JA-151ST-A Wireless combined smoke and heat detector with built-in siren
The detector communicates wirelessly and it is supplied by batteries (3x 1.5 V AA).
If the detector is operated without being assigned to a control panel or if communication with the control panel has been lost, it works in an autonomous mode (EN 14604).
The detector indicates a dangerous situation optically with an integrated light and a siren. It is able to acoustically report:
- a fire alarm detected by the detector itself
- a fire alarm from the system (alarm triggered by another fire detector)
- another type of alarm (e.g. an intruder alarm)
- for alarms reported by the system, sections can be set for which the alarm will be indicated
The product contains two separate detectors – an optical smoke detector and a temperature detector. The optical smoke detector uses the diffused light principle. It is very sensitive to particles that are present in thick smoke. It is less sensitive to small particles produced by the burning of liquids such as e.g. alcohol. Therefore, a heat detector is integrated, which responds better to a fire developing heat quickly with a small amount of smoke.
The fire detectors should be installed by a trained installer with a valid Jablotron certificate. The detector is not designed for installation in industrial environments.
Technical specifications
Power | 3 x Alkaline battery type LR6 (AA) 1.5 V/2.4 Ah 3 x Lithium battery type FR6 (AA) 1.5 V/3.0 Ah Please note: Batteries are not included |
---|---|
Typical lifetime | ≥ 3 years |
Communication band | 868.1 MHz, Jablotron protocol |
Effective Radiated Power (ERP) | 10 mW |
Communication range | approx. 300 m (open area) |
Dimensions | diameter 126 mm, height 50 mm |
Weight | 150 g |
Smoke detection | optical light scattering |
Smoke detector sensitivity | m = 0.11 ÷ 0.13 dB/m pursuant to EN 14604:2005, EN 54-7 |
Heat detection | class A1 according to EN 54-5 |
Alarm temperature | +60 °C to +65 °C |
Operating temperature range | -10 °C to +70 °C |
Complies with | EN 54-5, EN-54-7, EN-25 |
Also complies with | ETSI EN 300 220-2, EN 50130-4, EN 55022 and EN 60950-1 |
Can be operated according to | ERC REC 70-03 |
Recommended screw | 2x ø 3.5 x 40 mm (countersunk head) |